Below is a summary of good practice and the key points of the parts of BS
5306
part 8 relating to the supply and distribution of extinguishers. Readers are
referred to the British Standard itself for full details and reminded that this
is a summary only.
This document is broken down into the following sections:
Throughout, references to the pertinent parts of the British Standards and/or
other legislation have been included as
footnotes.
Minimum Level of Cover
Attention is drawn to the fact that the levels detailed below are the
minimum levels specified (and exclude the additional extinguishers required
as spares1). There are many circumstances in which these levels
would need to be increased including:
- in areas where the likelihood of fire is above average.
- in areas where the intensity of any fire would particularly intense.
Points Applicable in All Cases
- Normally, extinguishers should be conspicuously sited where persons
following an escape route will readily see them2. E.g. near to room exits,
corridors, stairways, etc. There should be no point in any building that is
further away than 30m from an appropriate extinguisher3 and extinguishers
provided to deal with a special fire hazard should be sited accessibly near to
that hazard4.
- Extinguishers need to be appropriately wall-mounted5, and, along with
other portable fire fighting equipment, identified by signs6:
- Groups of fire equipment should be signed with a “fire point” sign.
- The units should have an identifying sign that explains their use.
- In any one floor of a building or single occupancy, all extinguishers
should be of the same method of operation. Furthermore, all extinguishers for
any one function (e.g. to cover class A hazards) should also be similar in shape,
appearance and colour7.
- Staff should be trained on using the equipment8.
- Sufficient spare extinguishers should be available so that discharged
extinguishers may be replaced immediately after use1.
- For safety and convenience reasons, 6 litre AFFF foam extinguishers that have
passed the electrical conductivity test of BS EN 3
are, in the vast majority of circumstances, a more appropriate recommendation9
than 9 litre water extinguishers of the same A-rating that have not passed
the electrical conductivity test of BS EN 3.
Class A Cover – Carbonaceous Solids - Generally Applicable in All Premises
and Occupancies
- For all floors in all buildings there should always be at least two class
A extinguishers10.
- The minimum total class A rating required for a floor is 26A10 except:
- For large floors (more than 400m²) there must be a minimum total class A
rating of 0.065×floor area (measured in m²)10. E.g. a room 30m×20m would, if
there were no special considerations, require 0.065×30×20 = 39A cover.
- For small single-occupancy buildings, with a total upper floor area
(i.e. excluding the ground floor, basements, etc) of less than 100m², the
minimum total class A rating required for all of these above-ground floors
is 13A10 (but still with the minimum two class A rated extinguishers per
floor). This exception does not include or apply to the ground floor
however.
Class B Cover – Liquids or Liquefiable Solids
The provision of cover for Class B hazards is a specialist subject and not
covered here - The reader should contact us for
further information, although further details are provided
here for reference.
Class C Cover – Gaseous Hazards
In all but some very exceptional cases, a gas leak should only be dealt with
by closing a control valve or plugging the leak - personnel should not be
encouraged to tackle these hazards in any other way. Refer to the standard for
details11.
Class D Cover – Hot Metal Hazards
It is not possible to make general recommendations for the provision of
extinguishers to protect against combustible metals (e.g. magnesium). Decisions
should be made solely by experts on a case-by-case basis. The use of
inappropriate equipment can make a situation far worse12.
Class F Cover – Fats & Cooking Oil Hazards
As with Class B above, the provision of cover for Class F hazards is also a
specialist subject. However, there are two points pertinent points:
- All deep fat frying situations should be covered by either Class F
extinguisher(s)15 or, in the case of
very large fryers with a surface area in excess of 0.4m², a fixed system.
- Other fat and cooking oil hazards may also require the provision of either
Class F extinguisher(s)16 or a fixed
system.
The reader should contact us for further
information, although further details are provided
here for reference.
Cover for Electrical Hazards
It is important to note that, as electricity does not burn, fires
involving electrical hazards are in fact always fires of another class with the additional complication of the presence of an electrical
hazard. Additionally, electrical equipment is unlikely to provide the major fuel source and fire
extinguishers should therefore be decided on the basis of the other hazards in the
area (class A are likely to apply in most cases)13.
However, all extinguishers sited near any electrical equipment that may be
involved in a fire, should be marked as suitable for use on electrical fires14.
The phrase “class E” is often misused to describe fires,
hazards and cover concerning electrical hazards.
However, there is no definition of a Class E in the standard BS
EN 2, the British Standards that specifies the “Classification of fires”.
Full Copies of Standards
The British Standards are covered by copyright and are not available freely. However, these can be purchased at
British Standard Online or alternatively, some libraries may carry copies of
the more common standards.
Footnotes and References
- As per BS 5306: Part 8: 2000, clause 6.9
- As per BS 5306: Part 8: 2000, clause 7.1
- As per BS 5306: Part 8: 2000, clause 7.3
- As per BS 5306: Part 8: 2000, clause 7.4
- As per BS 5306: Part 8: 2000, clause 7.2
- As per BS 5306: Part 8: 2000, clause 7.1, BS5499:
Part 1, Fire Precautions (Workplace) Regulations and the Health & Safety
(Safety Signs & Signals) Regulations: 1996.
- As per BS 5306: Part 8: 2000, clause 4.4
- As per BS 5306: Part 8: 2000, clause 4.3
- As per BS 5306: Part 8: 2000, clauses 4.5 and 5.3
- As per BS 5306: Part 8: 2000, clause 6.2
- As per BS 5306: Part 8: 2000, clauses 5.2 and 6.5
- As per BS 5306: Part 8: 2000, clauses 5.2 and 6.6
- As per BS 5306: Part 8: 2000, clause 6.7.
- As per BS 5306: Part 8: 2000, clauses 5.3 and
6.7. There are some qualifications here, however, and the reader is referred
to the Standard for full details.
- As per BS 5306: Part 8: 2000, clauses 5.4 and
clause 6.8, Table 2.
- As per BS 5306: Part 8: 2000, clause 6.8.
|