Visit our home page by clicking here. Call us on 0345 3000 440, or simply click here on your smartphone.


  


All sales and services are subject to our Standard Terms & Conditions of Trading.

Use of this website constitutes acceptance of our Website Terms & Conditions of Use.

If you have any questions or comments about this web site,
please contact us.

Copyright © 1997-2021
Anderstore Ltd




email this   print this
Library: Standards: BS 5306-8:2012 Class B



   British Standards :
   BS 5266
      BS 5266-1
      BS 5266-7
      BS 5266-8
   BS 5306
      BS 5306-1
      BS 5306-3
      BS 5306-8
         BS 5306-8 B
         BS 5306-8 C, D
         BS 5306-8 F
      BS 5306-9
   BS 5499
   BS 7671
   BS 5839
     BS 5839-1
     BS 5839-6
   BS 7937
   BS EN 2:1992
   BS EN 3
   BS EN 54
   BS EN 671
     BS EN 671-3
   BS EN 1869
   BS EN ISO 9001
   BSI’s PAS 79

BAFE Schemes :
   SP101 & ST104
   SP203-1

Other Items :
   CE Marking


Introduction

The purpose of this page is to provide further information regarding the provision of Class B cover in accordance with the recommendations of BS 5306-8:2012. Readers are referred to the British Standard itself for full details and reminded that this is a summary only.

Throughout, references to the pertinent parts of the British Standards and/or other legislation have been included as footnotes.

Further Detail for Class B Cover

The assessment of cover for a single liquid container in a given room is calculated via the total surface area of the container and the table below1. This table gives the maximum surface area (in m²) for which a given rated extinguisher(s) is(are) suitable.

Maximum class B surface area e.g. Circle of diameter Minimum quantity and rating for each extinguisher
0.14 m² 0.42 m 1 × 21B 
0.23 m² 0.54 m 1 × 34B 
0.37 m² 0.69 m 1 × 55B 
0.47 m² 0.77 m 1 × 70B 
0.59 m² 0.87 m 1 × 89B 
0.75 m² 0.98 m 1 × 113B 
0.96 m² 1.11 m 1 × 144B 
1.22 m² 1.25 m 1 × 183B 
1.41 m² 1.34 m 2 × 113B 
1.80 m² 1.51 m 2 × 144B 
2.29 m² 1.71 m 2 × 183B 
2.88 m² 1.91 m 3 × 144B 
3.66 m² 2.16 m 3 × 183B 
4.66 m² 2.44 m 3 × 233B 

For example, a room containing a flammable liquid container measuring 1m×0.5m has an area of 1×0.5 = 0.5m² which requires 1×89B. Note, this cover does not include the spillage cover given below.

  • In cases where there are multiple containers less than 2m apart, they should be considered as an undivided container equivalent to a single container with a surface area equal to the total surface area of the group2.
  • In cases where there are multiple containers that are more than 2m and less than 20m apart, they should be considered as forming a divided group. The surface area of the largest single container, the total surface area of the largest undivided group (as above), or one third of the total surface area of all of the containers, whichever is the greater, is used to calculate the minimum rating3.
  • In cases where the containers are more than 20m apart, the containers should be considered on an individual basis4.
  • Additional extinguishers should also be supplied to cover the hazard from spillage. The recommended minimum rating = 10×Anticipated Spillage Volume (in litres)5. Refer to the British Standard for full details.
  • The table above gives minimum cover levels. Additional extinguishers should be provided where the liquids have a low fire point, or are particularly difficult to extinguish6.
  • Where high rated extinguishers are installed, additional low rated extinguishers should be provided and sited near any anticipated points of fire occurrence6.
  • Where such fire hazards also require a fixed system, a class B extinguisher(s) is nonetheless also required to cover the risk of spillage or fires outside of the fixed system’s coverage6.

  • Where such fire hazards are in areas prone to still air (where Class B fires are harder to extinguish) additional class B extinguisher(s) should be provided6.
  • Class B extinguishers should be sited such that there is not necessary to travel further than 10m to the site of any potential class B fire7. These travel distances should be reduced if there are doorways on this route7.
Full Copies of British Standards

The British Standards are covered by copyright and are not available freely. However, these can be purchased at British Standard Online or alternatively, some libraries may carry copies of the more common standards.

Footnotes and References
  1. As per BS 5306-8:2012, clause 8.3.2.2, Table 1.
  2. As per BS 5306-8:2012, clause 8.3.2.3.
  3. As per BS 5306-8:2012, clause 8.3.2.4.
  4. As per BS 5306-8:2012, clause 8.3.2.1 and 8.3.2.2.
  5. As per BS 5306-8:2012, clause 8.3.2.5.
  6. As per BS 5306-8:2012, clause 8.3.3.
  7. As per BS 5306-8:2012, clause 6.4.






We are members of FIA, the Fire Industry Association (formerly FETA and the BFPSA). Click here to find out more. We've over 70 years experience with parts of our group having been trading since 1947! Click here to find out more. We are BS EN ISO 9001:2015 certified by the UKAS-accredited independent third party, BSI. Click here to find out more. We are registered with BAFE, the British Approvals for Fire Equipment. Click here to find out more. We are members of the IFE, the Institution of Fire Engineers. Click here to find out more. We carry comprehensive Public & Product Liability and/or Professional Indemnity Insurance up to the value of a staggering £5m! Click here to find out more. We are members of IFEDA, the Independent Fire Engineering & Distributors Association. Click here to find out more.